Battery Module BATT123DIN, 3.2Ah, 12 Vdc, DIN-Rail
BATT123DIN
DIN-rail battery bank: 1 battery 3.2Ah + chassis, output 12 Vdc
- Output voltage: 12 Vdc
- Short-circuit protection
- Operating time in minutes
- Compact size
- Ambient temperature: 5 ÷ 40°C
- IP20

BaBattery modules: 12 Vdc
Features / Battery Characteristics
Battery Modules | 12 Vdc | |
Standard Version Code: | BATT 123 | BATT 127 |
DIN rail code / DIN Rail Version Code: | BATT 123 DIN | BATT 127 DIN |
End-of-charge voltage (trickle charge) / End-of-charge voltage | 27.5 Vdc (20°C) ; 27 Vdc (30°C); 26.5 Vdc (40°C) | |
Maximum permissible charging current / Maximum charging current | 0.80 A | 1.70 A |
Short-circuit protection / Short-circuit protection | Yes / Present | |
Protection fuse / Protection blade fuse | 25 A | |
Ambient temperature (operation) / Operating ambient temperature | +5 ÷ +40 °C | |
Ambient temperature (storage) / Storage ambient temperature | -20 ÷ +50 °C | |
Self-discharge rate / Self-discharge | 20 °C 15% per month / 20 °C 15% of charge per month | |
General data / General Characteristics
Dimensions (w-h-d) / Dimensions (w-h-d) mm | 105x136x90 | 105x153x123 |
Weight / Weight | 1.6Kg approx | 2.4Kg approx |
Protection class / Degree of protection | IP20 | |
Standard Version Assembly / Standard Version Mounting Type | FoSuspended mounting with M4 screws / With M4 screws | |
DIN rail mounting / DIN mounting | AvailablAvailable only on BATT xxx DIN code | |
Buffering time (min) / Autonomy (min.)
Code / Code: | Ba1.2 Ah battery | Ba3 Ah battery | Ba7.2 Ah battery | Ba12 Ah battery |
Load 1.5 A | 20 | 60 | 200 | 400 |
Load 3 A | 5 | 30 | 120 | 240 |
Load 5 A | 1.5 | 15 | 55 | 100 |
Load 7.5 A | No | 10 | 30 | 60 |
Load 10 A | No | 7 | 20 | 45 |
Load / Load 12 A | No | 3 | 12 | 30 |
Load 15 A | No | No | 9 | 20 |
Load 20 A | No | No | 7 | 13 |